UPS YUNTO P Series (250/500/750/1250) connector pinout

layout
schematic diagram

add this page to bookmarks

9 pin D-SUB FEMALE connector pin-out & layout
9 pin D-SUB FEMALE connector  at the UPS
Pin Name Dir Description
1 Battery Mode out This pin is shorted to PIN 5 (ground) if the mains power supply fails or is out of tolerance. (NORMALLY OPEN)
2 - - -
3 - - -
4 - - -
5 Ground - Ground terminal and common root of contacts at PIN 1, 8 and 9
6 - - -
7 UPS shut-down IN If a positive signal level (+5V to +12V DC) is applied, the UPS system switches off (PIN 5 is ground)
8 Battery Capacity Low OUT This pin is shorted to PIN 5 (ground) if the batteries have been discharged to such an extent that the remaining stored energy time is less than 2 minutes. (NORMALLY OPEN)
9 Battery Mode OUT The connection between this pin and PIN 5 (ground) is disconnected if the main power supply fails oe is out of tolerance. (NORMALLY CLOSED)

Note: Direction is relative to UPS.

This information should be correct, but may be not. You can help us to improve this webpage!
You can confirm this document to be correct (be careful), or report an error in document (error may be described in the following webpage). Result of your submission will be used for calculating document status shown at the bottom of this page.
Pinouts.ru > Pinouts of different devices connectors >  Pinout of UPS YUNTO P Series (250/500/750/1250) connector and layout of 9 pin D-SUB FEMALE connector

Source(s): Hardware Book
Document status: unknown
mark as erroneous!
mark as correct
0 report(s)
Click one of this links to change document status.
[Discuss at the forum] [Back to index] [Add new pinout]
[Report an error or update]
This information is maintained by pinouts.ru team and provided as a guideline only.
Efforts have been made to ensure it is correct, but it is the responsibility of the user
to verify the data is correct for their application.
52 hits since February 12, 2005